In this paper some aspects concerning the calibration uncertainty of three-axis low-cost accelerometers for possible use in diagnostics of civil buildings are considered, using a linear slide and a laser vibrometer as the reference. In order to analyse the principal and cross sensitivity and the offset of the sensor in dynamic conditions, the sensitivity matrix method has been used. Some considerations about the operating limits of a low-cost embedded system with MEMS accelerometer have been discussed, with reference to the calibration procedure. In particular, the effects of the non-constant sampling and of the achievable sampling rate, are studied with reference to the calibration uncertainty and to the capability of the calibration procedure to assess the best metrological performances of the system under test.

Identification of calibration and operating limits of a low-cost embedded system with MEMS accelerometer / D'Emilia, G.; Di Gasbarro, D.; Gaspari, A.; Natale, E.. - In: JOURNAL OF PHYSICS. CONFERENCE SERIES. - ISSN 1742-6588. - 882:1(2017). (Intervento presentato al convegno 24th A.I.VE.LA. Annual Meeting; Faculty of EngineeringBrescia; Italy; 27 October 2016 through 28 October 2016; Code 130382 tenutosi a Brescia nel 27-28 Ottobre 2016) [10.1088/1742-6596/882/1/012006].

Identification of calibration and operating limits of a low-cost embedded system with MEMS accelerometer

Gaspari A.;
2017-01-01

Abstract

In this paper some aspects concerning the calibration uncertainty of three-axis low-cost accelerometers for possible use in diagnostics of civil buildings are considered, using a linear slide and a laser vibrometer as the reference. In order to analyse the principal and cross sensitivity and the offset of the sensor in dynamic conditions, the sensitivity matrix method has been used. Some considerations about the operating limits of a low-cost embedded system with MEMS accelerometer have been discussed, with reference to the calibration procedure. In particular, the effects of the non-constant sampling and of the achievable sampling rate, are studied with reference to the calibration uncertainty and to the capability of the calibration procedure to assess the best metrological performances of the system under test.
2017
24th A.I.VE.LA. Annual Meeting; Faculty of EngineeringBrescia; Italy; 27 October 2016 through 28 October 2016; Code 130382
Identification of calibration and operating limits of a low-cost embedded system with MEMS accelerometer / D'Emilia, G.; Di Gasbarro, D.; Gaspari, A.; Natale, E.. - In: JOURNAL OF PHYSICS. CONFERENCE SERIES. - ISSN 1742-6588. - 882:1(2017). (Intervento presentato al convegno 24th A.I.VE.LA. Annual Meeting; Faculty of EngineeringBrescia; Italy; 27 October 2016 through 28 October 2016; Code 130382 tenutosi a Brescia nel 27-28 Ottobre 2016) [10.1088/1742-6596/882/1/012006].
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11589/239161
Citazioni
  • Scopus 10
  • ???jsp.display-item.citation.isi??? 6
social impact